Slow closing check valve

365bet足球投注网 - Check valve - Slow check valve

JD745X Multifunctional Water Pump Control Valve

JD745X Multifunctional Water Pump Control Valve Structure
JD745X Multifunctional Water Pump Control Valve Structure

JD745X multifunctional water pump control valve is suitable for industrial, mining, enterprise, high-rise buildings directly from the water supply and drainage system of the pump, to prevent and reduce the water hammer of the pipeline when the pump is opened and closed, to prevent water backflow, to protect the pump, to maintain the safety of the pipeline, and to have a stop valve , Check valve, electric valve and water hammer eliminator four functions. It is especially suitable for supporting automatic control systems. It does not require an electrical control cabinet and external power. It automatically opens and closes according to the routine. It has three functions of quick closing, slow closing, and energy absorption cavity to prevent and eliminate water hammer, which can effectively improve the safety and reliability of the system. Meet the requirements of system engineering equipment automation control.

working principle

  1. Before the pump starts, the pressure at the valve outlet end acts on the main valve plate, and the valve is in the closed position. At the same time, the upper cavity of the diaphragm controller communicates with pressure water, and the lower cavity communicates with the low pressure at the inlet end of the valve.
  2. After the pump is started, the pressure at the valve inlet gradually increases, and at the same time, the pressure water slowly enters the lower cavity of the diaphragm controller through the connecting pipe at the valve inlet to realize the slow opening of the main valve plate. The opening speed can be adjusted by the control valve.
  3. When the pump stops, the pressure at the valve inlet decreases. When the flow is close to zero, the main valve plate closes quickly under its own gravity. As the pressure at the inlet of the valve decreases, the pressure water at the outlet of the valve enters the upper cavity of the diaphragm controller through the connecting tube, and the water in the lower cavity is pressed back to the inlet of the valve through the connecting tube at the inlet of the valve. The slow-closing valve plate closes slowly. Adjusted by control valve. The quick-closing of the main valve plate and the slow-closing of the slow-closing valve plate comply with the two-phase closing rule, which can effectively eliminate water hammer.

Structural features

  1. No operational controls are required. The water pressure difference between the valve before and after the pump starts and stops is used as the control power, and it has the function of automatic opening and closing as the pump opens and closes.
  2. The opening and closing of the valve can effectively prevent accidents caused by the rise of water hammer pressure waves. According to the field usage survey and actual measurement, the peak pressure of the water hammer when the pump is stopped are all within 1.3 times the working pressure.
  3. No on-site debugging is required, and the applicable working range is wide.
  4. Maintenance-free. Because one valve replaces three valves, the maintenance and repair workload is greatly reduced.
  5. Small resistance loss. Adopting streamlined, wide valve body design, resistance loss is reduced by more than 50% compared with similar foreign products. For example, when the DN200 product is operating at an economic flow rate of v = 2m / s, the multi-functional pump control valve loss is 0.7m, while similar foreign products It is 1.5m.

Implementation standards

Design specification QB / T219
Structure length QB / T219
Test and inspection GB / T13927
Flange connection JB / T79, GB9112 ~ 9131, HG20592, SH3406, ANSI B16.5
Product Identification GB / T 12220
Delivery specifications JB / T 7928

Technical Parameters

Nominal pressure
(Mpa)
Shell test pressure
(MPa)
Seal test pressure
(MPa)
Slow closing time
(s)
Minimum operating pressure
(MPa)
Applicable medium Medium temperature
(℃)
1.0 1.5 1.1 3-60
(Adjustable)
≥0.07 water 0-80
1.6 2.4 1.76
2.5 3.75 2.75

Part material

Part Name Parts material
Body valve cover HT200, QT350, WCB
Valve seat Copper alloy / 2Cr13
O-ring seal Nitrile rubber
Valve stem 2Cr13
spring 50CrVA
Cylinder liner piston (piston type) 2Cr13
Diaphragm (diaphragm type) Fabric with nitrile rubber
Regulating valve Copper alloy
filter stainless steel

Dimension table

DN L H D D1 nd
1.0MPa 1.6MPo 2.5MPa 1.0MPa 1.6MPa 2 5MPa 1.0MPa 1.6MPa 2.5MPa
50 205 293 165 165 165 125 125 125 4-18 4-18 4-18
65 216 328 185 185 185 145 145 145 4-18 4-18 8-18
80 250 364 200 200 200 160 160 160 8-18 8-18 8-18
100 320 418 220 220 235 180 180 190 8-18 8-18 8-22
125 365 481 250 250 270 210 210 220 8-18 8-18 8-22
150 415 543 285 285 300 240 240 250 8-22 8-22 8-26
200 500 673 340 340 360 295 295 310 8-22 12-22 8-26
250 605 792 395 405 425 350 355 370 12-22 12-26 12-26
300 698 927 445 460 485 400 410 430 12-22 12-26 12-30
350 787 957 505 520 555 460 470 490 16-22 16-26 16-30
400 914 1188 565 580 620 515 525 550 16-26 16-30 16-33
450 978 1218 615 640 670 565 585 600 20-26 20-30 16-36
500 978 1256 670 715 730 620 650 660 20-26 20-33 20-36
600 1200 1600 780 840 725 770 20-30 20-36 20-36
700 1450 1750 895 910 840 840 24-30 24-36
800 1560 1900 1015 1025 950 950 24-33 24-39
900 1800 2100 1115 1050 28-33
1000 2000 2400 1230 1160 28-36